Airflow Transducer 6332/6332D


Features

  • 10 interchangeable probe options
  • Probes quickly and easily attach/detach
  • Digital Display Option (model 6332D)
  • Selectable Output (Output can be set to either voltage (0 to 5V) or current (4 to 20mA))

Applications

  • Product Line Quality Control Quality: Control monitoring and controlling air velocity and distribution during drying/ shaping process.
  • PCB Temperature monitoring: Combined with thermographic system measure air velocity across the board to evaluate the cooling efficiency.
  • Air Velocity Monitor for Local Exhaust Ventilation and FFU (Fan Filter Unit): Prevent exposure of hazardous materials to workers and prevent leakage by thorough monitoring and control of chamber airflow.
  • Residential Air Ventilation Monitoring Ensure ventilation system efficiency by actively monitoring system balance and controlling airflow.

SPECIFICATIONS:

Model
6332 / 6332D
 Measuring Object

Clean air and compatible, non-combustible gases

 Measuring Range

Maximum range 0.1 ~ 50 m/s  (Range dependant on probe type*)

 Temperature Compensation Range

0.1-4.99 m/s
5.00-9.99 m/s
10.0-24.9 m/s
25.0-50.0 m/s
5~40°C
±0.25 m/s
±0.50 m/s
±1.25 m/s
±2.50 m/s
40~80°C
±0.35 m/s
±0.70 m/s
±1.75 m/s
±3.50 m/s
 Selectable Output Optio
(Set via onboard DIPswitch).

Current output: DC 4~20mA (Max. load resistance: 250Ω)

Voltage output: DC 0~5V

 Selectable Range Option

(Rotary Switch selectable).

0~2, 0~5, 0~10, 0~25, or 0~50 m/s

 Display Resolution
(Model 6332D only)

Velocity Range: 0~2, 0~5, 0~10 m/s  --  Display Resolution: 0.01m/s
Velocity Range: 0~25, 0~50 m/s  --  Display Resolution: 0.1m/s

Power Supply

DC 12~24V

Power Consumption (Reference Value)

Approx. 2.0W (Under the following conditions - power supply: 12V, air velocity: approx. 10m/s, using a unit with a display with probe model 0965-03.) 

Power consumption rate is subject to change according to conditions such as air velocity, probe type and use of display.

Connection Wire Size

0.5 ~ 1.5 mm2

Operating Temperature Range

5 ~ 40°C

Storage Temperature Range

-10 ~ 50°C

Dimensions

Approx. 128(W)×78(D)×30(H) mm

Weight

Approx. 320g (11oz.)

Standard Accessory

Operation Manual : 1,  Main Unit Case: 1

Optional Accessory

Probe Cable (10m, 20m, 30m), Display Unit (Supplied with a case with a display window and 2 installation screws.), Dedicated AC Adapter (DC12V)

0962-00, 0963-00 0.1~50.0m/s Uni-directional
0964-01, 0964-02 Omni-directional (Needle)
0965-00, 0965-01 0.1~25.0m/s Omni-directional (Spherical)
0965-03, 0965-04 0.1~25.0m/s

Mini-temperature-compensation-sensor integrated type

Omni-directional (Spherical)

0965-07, 0965-08

Mini-temperature-compensation-sensor independent type

Omni-directional (Spherical)

 


  
Product Price
Airflow Transducer 6332 $505.00
Airflow Transducer 6332D (w/ display) $715.00
AC Adaptor $47.00
Probe Cable (2m) 1504-02 $85.00
Probe Cable (5m) 1504-03 $85.00
Probe Cable (10m) 1504-04 $85.00
Probe Cable (20m) 1504-05 $85.00
Probe Cable (30m) 1504-06 $100.00
Uni-directional probe 0962-00 $280.00
Uni-directional probe 0963-00 $280.00
Omni-Directional probe (400mm) 0964-02 $380.00
Omni-Directional probe (with horn) 0965-00 $490.00
Omni-Directional probe (without horn) 0965-01 $480.00
Omni Directional, mini straight type, temp.compensation, 0965-03 $480.00
Omni Directional, mini L-shape type, temp.compensation, 0965-04 $480.00
Omni Directional, mini straight type, separated temp.compensation, 0965-07 $480.00
Omni Directional, mini L-shape type, separated temp.compensation, 0965-08 $490.00  

Topac Inc. 231 CJC Highway, Suite 103 Cohasset MA 02025 USA
Tel: 781 740 8778 Fax: 781 740 8779

| E-mail | Home | Digital Thermometers | Related |