Slim-type thermocouple temperature transducer (TH-2C)

     Features
  • AC power supply 100 - 240V AC
  • DIN rail mounting
  • Input/Output/Power supply isolated
  • This unit is a slim-type signal converter with a thickness of 12.5 mm. This temperature transducer insulates the three input, output, and power ports, inputs thermocouple sensor signals, and outputs DC signals. Multiple units of this temperature transducer can be closely installed, achieving space saving at the installation location. This unit works on AC power.
  • download .pdf file

TH-2C Common Specifications
Base Accuracy
±0.2% F.S (25±2ºC)
Power Supply Variation ±0.06 % F.S
Load resistance variation ±0.06% F.S
Temperature characterisitc ±0.02 % F.S/ºC
Accuracy of cold junction compensation ±1ºC (10 to 30ºC) / ±2ºC (other than 10 to 30ºC)
Disconnection detection Upside (135±15% F.S)
Response Time 200 msec (TYP) (0-90%)
Front adjustments ±5% for zero and span
Insulation resistance Between input and output/power supply: more than 100Mohm at 500VDC
Dielectric strength Between input and output/power supply: for 1 min at 1500VAC
Power supply voltage 24VDC ±10% (TH-5C)
100 - 240 V AC +/- 10% (TH-2C)
Consuming current Less than 50mA (at 24 VDC) //Less than 20 mA (at 100V AC)
Operating ambient temp -5 - 50ºC
Operating ambient humidity Less than 90% RH (No-condensing)
Storage Temp -10 to 70ºC
Storage Humidity Less than 60% RH (no condensing)
weight approx 80g
 
 
INPUT MODULES -
 
Code # Thermocouple Input Signal For Code Y
J0
J
0 to 1000ºC -50 to 1000ºC span
200 to 1050ºC
JY other than above -->
K2
K
-50 to 200ºC -50 to 1200ºC span
200 to 1250ºC
K3 0 to 200ºC
K4 -50 to 1200ºC
K5 0 to 1200ºC
KY -->
R0
R
0 to 1700ºC 0 to 1700ºC span
400 to 1700ºC
RY -->
S0
S
0 to 1700ºC 0 to 1700ºC span
500 to 1700ºC
SY -->
T0
T
-50 to 350ºC -50 to 350ºC span
200 to 400ºC
T1 0 to 350ºC
TY -->
 
OUTPUT MODULES -
 
Code # Output Signal Allowable Load Resistance
0 0 - 5V DC More than 2 Kohm
1 1 - 5V DC
2 0 - 10V DC More than 4 Kohm, negative output: more than 10Kohm
3 -10 - 10V DC
A 4 - 20mA DC Less than 550ohm
Y Specifications limit:
Voltage output: -10 to 10V DC
Minimum Span:1 to 20V
Current output: 0 - 20mA DC
Minimum Span: 1- 20 mA

   

Ordering Information
TH-2C Configure Input/Output in Store
$371.00
 

Topac Inc. 231 CJC Highway, Suite 103 Cohasset MA 02025 USA
Tel: 781 740 8778 Fax: 781 740 8779
e-mail: sales@topac.com